Article 22 Floodlights - Super Cup

Regulations of the UEFA Super Cup

FT_ContentType_custom
Competition Regulations
FT_Category_Only_Custom
Clubs
FT_Competition
SCUP
FullSeasonYears
2021
EnforcementDate
1 July 2021
22.01

The host association must ensure that the stadium is equipped with floodlights, guaranteeing the average level of horizontal illuminance must be at least 1,500 Eh (lux) and the uniformity ratios must be U1 > 0.5 and U2 > 0.7. The average level of vertical illuminance must be at least 1,250 Ev (lux) and the uniformity ratios must be U1 > 0.4 and U2 > 0.5. All glare ratings (RG) must be less than 50. The pitch illuminance levels should have a colour rendering (Ra) of at least 80.